Installation Instructions
Part No. 8316557
IMPORTANT:
Read and save
COMMERCIAL
these instructions
ELECTRONIC DRYER
IMPORTANT
GAS ELECTRIC
Installer: Leave Installation Instructions
with the owner.
120-volt, 60 Hz 120/240-volt, 60 Hz
Owner: Keep Installation Instructions for
future reference.
Save Installation Instructions for local
®
electrical inspector’s use.
COMMERCIAL
LAUNDRY
PRODUCTS
Exhaust
requirements
Metal flexible vent must be fully
extended and supported when the
dryer is in its final position. DO NOT
KINK OR CRUSH THE VENT. The metal
flexible vent must be completely
open to allow adequate exhaust air
to flow.
Allow as much room as possible
when using elbows or making turns.
Bend vent gradually to avoid kinking.
Remove excess flexible vent to avoid
sagging and kinking that may result in
reduced air flow.
For exhaust systems not covered by
the exhaust length chart, see
Whirlpool Service Manual, “Exhausting
Whirlpool Dryers,” Part No. 603197,
available from your Whirlpool parts
distributor.
WARNING
If dryer is installed in a confined area,
such as a bedroom, bathroom or
closet, it must be exhausted to the
outside and provision made for
enough air for combustion and
ventilation. (Check governing codes
and ordinances.) See “Recessed area
and closet installation instructions” on
Page 12.
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to do so can result in
death or fire.
Exhaust outlet is located at the
center of the bottom dryer back.
The exhaust vent can be routed up,
down, left, right, behind the dryer or
straight out the back of the dryer.
Do not use non-metal flexible vent,
metal vent that is smaller than four
inches in diameter or exhaust hoods with
magnetic latches.
Maximum length of exhaust system
depends upon the type of vent used,
number of elbows and type of
exhaust hood. The maximum length
for both rigid and flexible vent is
shown in the chart.
The dryer must be exhausted outdoors.
Do not exhaust dryer into a gas vent,
chimney, wall, ceiling, or concealed
space of a building.
EXHAUST HOOD TYPE
Do not install flexible vent in enclosed
walls, ceilings or floors.
4"
4"
(10.2 cm)
(10.2 cm)
If using an existing exhaust system, clean
lint from entire length of exhaust system.
Make sure exhaust hood is not plugged
with lint.
No. of
90°
turns
4"
The exhaust system should be inspected
and cleaned yearly.
(10.2 cm)
4"
2-1/2"
4"
(10.2 cm)
(10.2 cm)
(6.4 cm)
Replace any plastic or metal foil exhaust
vent with rigid metal or flexible metal
vent.
MAXIMUM LENGTH OF 4-INCH (10.2 cm) DIAMETER
RIGID METAL VENT
0
1
2
3
4
58 FT. (17.7 m)
64 FT. (19.5 m)
54 FT. (16.5 m)
44 FT. (13.4 m)
35 FT. (10.7 m)
27 FT. (8.2 m)
64 FT. (19.5 m)
54 FT. (16.5 m)
44 FT. (13.4 m)
35 FT. (10.7 m)
27 FT. (8.2 m)
Use 4" (10.2 cm) vent clamps to
secure vent system.
48 FT. (14.6 m)
38 FT. (11.6 m)
29 FT. (8.8 m)
21 FT. (6.4 m)
exhaust airflow
MAXIMUM LENGTH OF 4-INCH (10.2 cm) DIAMETER
FLEXIBLE METAL VENT
better
good
exhaust
airflow
exhaust
airflow
0
1
2
3
4
36 FT. (11.0 m)
31 FT. (9.4 m)
27 FT. (8.2 m)
25 FT. (7.6 m)
23 FT. (7.0 m)
36 FT. (11.0 m)
31 FT. (9.4 m)
27 FT. (8.2 m)
25 FT. (7.6 m)
23 FT. (7.0 m)
28 FT. (8.5 m)
23 FT. (7.0 m)
19 FT. (5.8 m)
17 FT. (5.2 m)
15 FT. (4.6 m)
Four-inch metal exhaust vent is required.
Plan installation to use the fewest
number of elbows and turns.
Page 3
An exhaust hood should cap the
outside end of the main vent to
prevent exhausted air from returning
to the dryers. If an exhaust hood
cannot be used, the outside end of
the main vent should have a sweep
elbow directed downward. If the
main vent travels vertically through
the roof, rather than through the wall,
install 180° sweep elbow on the end
of vent at least 2 feet (61 cm) above
the highest part of the building. The
opening wall or roof shall have a
diameter 1/2 inch (1.3 cm) larger than
the exhaust vent diameter. The
exhaust vent should be centered in
the opening.
An exhaust hood should cap the
exhaust vent to prevent exhausted air
from returning into the dryer. The
outlet of the hood must be at least
12 inches (30.5 cm) from the ground
or anything else that may be in the
path of the exhaust.
Gas Dryer
Gas requirements
Four-inch outlet hood is preferred.
However, a 2-1/2-inch (6.4 cm) outlet
exhaust hood may be used. A
2-1/2-inch (6.4 cm) outlet creates
greater back pressure than other
hood types. For permanent
WARNING
installation, a stationary exhaust
system is required.
Explosion Hazard
A main exhaust vent can be used for
exhausting a group of dryers. Main
exhaust vent should be sized to
Use a new AGA or CSA
approved gas supply line.
exhaust
remove 200 CFM of air per dryer.
Large-capacity lint screens of proper
design may be used in the main
exhaust vent if checked and cleaned
frequently. The room where the dryers
are located should have make-up air
equal to or greater than the CFM of
all the dryers in the room.
wall
hood or
sweep
elbow
Install a shut-off valve.
horizontal vent
Securely tighten all gas
connections.
If connected to LP, have a
qualified person make sure gas
pressure does not exceed 13"
(33 cm) water column. Examples
of a qualified person include
licensed heating personnel,
authorized gas company
main exhaust vent
wall
180°
sweep
elbow
2 ft. (61 cm)
min. above
highest point of
building
30° max.
personnel, and authorized
service personnel.
main collector vent
air flow
main collector
vent
Failure to do so can result in
death, explosion, or fire.
30° max.
30° max.
OBSERVE ALL GOVERNING CODES
AND ORDINANCES.
roof
Back-draft Damper Kits, Part No.
3391910, are available from your
Whirlpool dealer and should be
installed in each dryer's exhaust vent
to prevent exhausted air from
returning into the dryers and to keep
the exhaust in balance within the
main exhaust vent. Unobstructed air
openings are required.
Do Not install screening or cap over
end of vent.
A.The installation must conform
with local codes, or in the absence of
local codes with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54
installation codes.
B.The design of this dryer has
been certified by the CSA
Each exhaust vent should enter the
main vent at an angle pointing in the
direction of the airflow. Vents entering
from the opposite side should be
staggered to reduce the exhausted
air from interfering with the other
vents.
International for use at altitudes up to
10,000 feet (3048 m) above sea level
at the B.T.U. rating indicated on the
model/serial plate. Burner input
adjustments are not required when
the dryer is operated up to this
elevation.
The maximum angle of each vent
entering the main vent should be no
more than 30°.
When installed above 10,000 feet
(3048 m), a four percent (4%)
reduction of the burner B.T.U. rating
shown on the model/serial plate is
required for each 1,000 foot (305 m)
increase in elevation. For assistance
when converting to other gas types
and/or installing above 10,000 feet
(3048 m) elevation, contact your
local service company.
Keep air openings free of dry
cleaning fluid fumes. Fumes create
acids which, when drawn through the
dryer heating units, can damage
dryers and loads being dried.
A clean-out cover should be located
on the main exhaust vent for
periodically cleaning of the exhaust
system.
Page 4
A 120-volt, 60-Hz, AC-only, 15- or
20-ampere fused electrical supply is
required. A time-delay fuse or circuit
breaker is recommended.
C.
Check that dryer is equipped
H.
If local codes and ordinances
with the correct burner for the
particular type of gas used. Burner
information can be found on the
serial/rating plate in the door well of
the appliance. If this information does
not agree with the type of gas
available, see your dealer.
permit, it is recommended that new
flexible metal tubing, design-certified
by the AGA or CSA, be used for
connecting the dryer to the gas
supply line. (The gas feed pipe which
extends through the lower rear of the
dryer is provided with 3/8-inch metal
pipe thread.)
It is recommended that a separate
circuit serving only this appliance be
provided.
If codes permit and a separate ground
wire is used, it is recommended that a
qualified electrician determine that the
ground path is adequate.
D.This dryer is equipped for use
with NATURAL GAS. It is certified by
CSA International for manufactured,
mixed and L.P. (propane and
butane) gases with appropriate
conversion. No attempt shall be
made to convert the appliance from
the gas specified on the serial/rating
plate for use with a different gas
without consulting the serving gas
supplier. Conversion must be done by
a qualified service technician. Gas
conversion kit part numbers are listed
on the gas valve burner base.
I.
If rigid
pipe is used
as a gas supply line, a
combination of pipe fittings must
be used to obtain an in-line
connection to the dryer.
Recommended
ground method
The dryer, when installed, must be
electrically grounded in accordance
with local codes, or in the absence of
local codes, with the National
J.
Make sure that lower edges of
the cabinet, plus the back and
bottom sides of the dryer are free of
obstructions to permit adequate
clearance of air openings for
combustion air. See "Recessed area
and closet installation instructions,"
page 12, for minimum spacing
requirements.
Electrical Code, ANSI/NFPA 70*.
GROUNDING INSTRUCTIONS: This
appliance must be grounded. In the
event of malfunction or breakdown,
grounding will reduce the risk of
electric shock by providing a path of
least resistance for electric current.
E.Provide a rigid gas supply line of
1/2-inch IPS pipe to the dryer
location. If the total length of the
supply line is more than 20 feet
(6.1 m), larger pipe will be needed.
For L.P. gas usage, 3/8-inch,
K.
For ease of installation,
The power supply cord plug must be
plugged into an appropriate outlet
that is properly installed and
grounded in accordance with all
local codes and ordinances.
operation and servicing (if ever
needed) adequate space should be
provided around the dryer.
approved copper tubing may be
used. Pipe-joint compounds suitable
for use with L.P. gas should be used.
L.
A 1/8-inch NPT plugged tapping,
accessible for gauge testing, must be
installed immediately upstream of the
gas supply connection to the dryer.
WARNING - Improper connection of
the equipment-grounding conductor
can result in a risk of electric shock.
Check with a qualified electrician or
serviceman if you are in doubt as to
whether the appliance is properly
grounded. Do not modify the plug
provided with the appliance - if it will
not fit the outlet, have a proper outlet
installed by a qualified electrician.
shutoff valve
“open” position
to dryer
The dryer must be disconnected from
the gas supply piping system during
any pressure testing of the system at
test pressures in excess of 1/2 psig.
gas supply
line
The dryer must be isolated from the gas
supply piping system by closing the
equipment shut-off valve during any
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psi.
F. The supply line shall be equipped
with a shutoff valve installed within 6
ft. (1.8 m) of dryer in accordance with
the National Fuel Gas Code, ANSI
Z223.1 — latest edition*. This valve
should be located in the same room
as the dryer and should be in a
location that allows ease of opening
and closing. Do Not block access to
the shutoff valve.
3-prong ground-type
outlet
3-prong
ground
plug
Electrical
requirements
power
ground
WARNING
supply cord
prong
G.If the dryer is installed in a
confined area such as a bathroom or
closet, provision must be made for
enough air for combustion and
ventilation. (Check governing codes
and ordinances. or refer to the
section of this instruction covering
recessed and closet installations.)
Copies of the standards listed above may
be obtained from:
* National Fire Protection Association
One Batterymarch Park
Quincy, Massachusetts 02269
Electrical Shock Hazard
Plug into a grounded 3-prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions
can result in death, fire, or electrical
shock.
Important: Observe all governing
codes and ordinances.
Page 5
5.Move dryer close to final
position. Remove cardboard or
hardboard from under dryer.
Now Start...
10.To exhaust dryer, see Exhaust
requirements, Pages 3-4. Connect
exhaust vent system to dryer exhaust
outlet and exhaust hood using 4"
(10.2 cm) clamps. Use caulking to
seal exterior wall opening around
exhaust hood.
With dryer in laundry area.
WARNING
6.Remove red cap from gas pipe.
Carefully move dryer into final
position. Place level on top of the
dryer, first side to side; then front to
back. If the dryer is not level, adjust
the legs of the dryer up or down until
the dryer is level.
Excessive Weight Hazard
Use two or more people to move and
install dryer.
Failure to do so can result in back or
other injury.
11.Carefully move dryer into
final position. Place level on top of
the dryer, first side to side; then front
to back. If the dryer is not level, adjust
the legs of the dryer up or down until
the dryer is level.
7.Connect gas supply to dryer.
Use pipe-joint compound resistant to
the action of L.P. gas for gas
connections. If flexible metal tubing is
used, be certain there are no kinks.
3-prong,
ground-type
outlet
12.Plug power supply cord into
exhaust duct
grounded outlet.
13.Check dryer operation (some
accumulated time may be on the
timer due to factory testing).
If necessary for service, open the toe
panel, use a putty knife to press on
the toe panel lock located at the
center top of the toe panel. Pull
downward on the toe panel to open.
Toe panel is hinged at the bottom.
Pull timer-set button left. (Operating
time will accumulate per number of
depressions and type of timing cam
used.) Push START/RESTART button.
Using a full heat cycle (not the air
cycle), let the dryer run for at least
five minutes.
gas supply line
8.Open the shutoff valve in the
gas supply line.
Note: Dryer door must be closed for
dryer to operate. When door is open,
dryer stops, but timer continues to run.
To restart dryer, close door and push
START/RESTART button.
9.Use a non-corrosive leak
detection fluid to check for leaks.
Bubbles around connections will
indicate a leak. NEVER TEST FOR GAS
LEAKS WITH A FLAME. If a leak
appears, shut off gas valve controls
and adjust connections. Then check
connections again. Close toe panel.
All connections must be wrench-
tightened.
gas shutoff valve
1.Take tape off front corners of
dryer. Open dryer and remove the
literature and parts packages. Wipe
the interior of the drum thoroughly
with a damp cloth.
14.If the burner does not ignite
and you can feel no heat inside the
dryer, shut off dryer for five minutes.
Check that all supply valve controls
are in "ON" position and that the
electrical cord is plugged in. Repeat
five-minute test.
2.Take two of the cardboard
corners from the carton and place
them on the floor in back of the dryer.
Firmly grasp the body of the dryer
and gently lay it on its back on the
cardboard corners.
15.If drying time is too long,
make sure lint screen is clean.
3.With one of the legs in hand,
check the ridges for a diamond
marking. That's how far the leg is
supposed to go into the hole.
4.Start to screw the leveling legs
into the holes by hand. (Use a small
amount of liquid detergent to
lubricate the screw threads so it is
easier to turn the legs.) Use a 1-inch
wrench or socket wrench to finish
turning the legs until you reach the
diamond mark.
Now stand the dryer up.
Slide dryer onto cardboard or
hardboard before moving across floor
to avoid damaging floor covering.
Page 6
Now Start...
Electric Dryer
WARNING
Electrical
Excessive Weight Hazard
requirements
Use two or more people to move and
install dryer.
Failure to do so can result in back or
other injury.
If codes permit and a separate
ground wire is used, it is
recommended that a qualified
electrician determine that the ground
path is adequate.
With dryer in laundry area...
Important: Observe all governing
codes and ordinances.
fuse
disconnect
box
exhaust
vent
system
A four-wire or three-wire, single-
phase, 120/240-volt, 60-Hz, AC-only
electrical supply (or four-wire or three-
wire, 120/208-volt, if specified on the
model/serial rating plate) is required
on a separate, 30-ampere circuit,
fused on both sides of the line. A time-
delay fuse or circuit breaker is
recommended.
30-amp
outlet
Recommended
ground method
It is the personal responsibility and
obligation of the customer to contact
a qualified electrician to assure that
the electrical installation is adequate
and in conformance with the
1.Take tape off front corners of
dryer. Open dryer and remove the
literature and parts packages. Wipe
the interior of the drum thoroughly
with a damp cloth.
National Electrical Code, ANSI/NFPA
70 — latest edition*, and all local
codes and ordinances.
2.Take two of the cardboard
corners from the carton and place
them on the floor in back of the dryer.
Firmly grasp the body of the dryer
and gently lay it on its back on the
cardboard corners.
Copies of the standards listed above may
be obtained from:
* National Fire Protection Association
One Batterymarch Park
Quincy, Massachusetts 02269
3.With one of the legs in hand,
check the ridges for a diamond
marking. That's how far the leg is
supposed to go into the hole.
4.Start to screw the leveling legs
into the holes by hand. (Use a small
amount of liquid detergent to
lubricate the screw threads so it is
easier to turn the legs.) Use a 1-inch
wrench or socket wrench to finish
turning the legs until you reach the
diamond mark.
Now stand the dryer up.
Slide dryer onto cardboard or
hardboard before moving across floor
to avoid damaging floor covering.
5.Move dryer close to final
position. Remove cardboard or
hardboard from under dryer.
Page 7
Power supply cord
Direct wire
6.Make electrical connection.
This dryer is manufactured with the
cabinet-ground conductor
connected to the NEUTRAL (center) of
the wiring harness at the terminal
block. If local codes do NOT permit
this type of connection, use “Four-
wire connection” instructions.
Use a new UL-approved power supply
cord rated 240-volt min., 30 amperes
and marked for use with a clothes
dryer.
WARNING
WARNING
Fire Hazard
Use 10 gauge solid copper wire.
Use a UL approved strain relief.
For a grounded, cord-connected
appliance —
GROUNDING INSTRUCTIONS:
Disconnect power before making
electrical connections.
This appliance must be grounded. In
the event of malfunction or
breakdown, grounding will reduce
the risk of electric shock by providing
a path of least resistance for electric
current.
Fire Hazard
Use a new UL approved 30
ampere power supply cord.
Connect neutral wire (white or
center wire) to center terminal
(silver).
Use a UL approved strain relief.
Ground wire (green or bare wire)
must be connected to green
ground connector.
Disconnect power before making
electrical connections.
If using a power supply cord, the plug
must be plugged into an appropriate
outlet that is properly installed and
grounded in accordance with all
local codes and ordinances.
Connect neutral wire (white or
center wire) to center terminal
(silver).
Connect remaining 2 supply
wires to remaining 2 terminals
(gold).
Ground wire (green or bare wire)
must be connected to green
ground connector.
WARNING - Improper connection of
the equipment-grounding conductor
can result in a risk of electric shock.
Check with a qualified electrician or
serviceman if you are in doubt as to
whether the appliance is properly
grounded. Do not modify the plug
provided with the appliance - if it will
not fit the outlet, have a proper outlet
installed by a qualified electrician.
Securely tighten all electrical
connections.
Failure to do so can result in
death, fire, or electrical shock.
Connect remaining 2 supply
wires to remaining 2 terminals
(gold).
Securely tighten all electrical
connections.
Failure to do so can result in
death, fire, or electrical shock.
For a permanently connected
appliance —
GROUNDING INSTRUCTIONS:
This appliance must be connected to
a grounded metal, permanent wiring
system; or an equipment-grounding
conductor must be run with the
circuit conductors and connected to
the equipment-grounding terminal or
lead on the appliance.
1. Disconnect the power supply.
dryer
strain
cabinet
relief
clamp
sections
external ground
conductor screw
strain relief
screws
tab
3. Assemble
hold-
terminal
down
3/4" U.L.-listed strain relief
block
screw
(U.L. marking on strain relief) into the
hole below terminal block opening.
Tighten strain relief screws just enough
to hold the two clamp sections
cover
2. Remove hold-down screw
together. Install power supply
and terminal block cover.
cord/cable through the strain relief.
Complete installation following
instructions for your type of
connection:
• Four-wire (recommended method)
• Three-wire (if four-wire is not
available)
Page 8
Four-wire connection...
Four-wire receptacle (required for mobile homes)
POWER SUPPLY CORD
4. Remove center terminal block
screw.
5. Remove appliance ground wire
(green with yellow stripes) from
external ground connector screw.
Fasten under center, silver-colored
terminal block screw.
spade
terminals with
upturned ends
6. Connect ground wire (green) of
power supply cord to external
ground conductor screw. Tighten
screw.
3/4" U.L.-listed
NEUTRAL (white)
NEUTRAL
strain relief
7. Connect neutral wire (white or
center) of power supply cord under
center screw of the terminal block.
Tighten screw.
ground prong
ground wire
(green)
ring terminals
8. Connect the other wires to outer
terminal block screws. Tighten screws.
Four-wire power supply cord must have
four, No.-10 copper wires and match a
four-wire receptacle of NEMA Type
14-30R. The fourth wire (ground
9. Tighten strain relief screws.
conductor) must be identified with a
green cover and the neutral
conductor by a white cover.
10. Insert tab of terminal block cover
into slot of the dryer rear panel. Secure
cover with hold-down screw.
DIRECT WIRE
4. Remove center terminal block screw.
5. Remove appliance ground wire
(green with yellow stripes) from
external ground connector screw.
Fasten under center, silver-colored
terminal block screw.
Preparing the wire:
3-1/2" (8.9 cm)
3/4" U.L.-
listed strain
relief
1" (2.5 cm)
of wires
stripped of
insulation
6. Connect the ground wire (bare)
of the power supply cable to the
external ground conductor screw.
Tighten screw.
to
disconnect
box
NEUTRAL wire
(white or center)
7. Place the hooked end of the
neutral wire (white or center) of
power supply cable under the center
screw of terminal block (hook facing
right). Squeeze hook end together.
Tighten screw.
bare ground
wire
10-gauge, 3-wire
with ground wire
(Romex)
5" (12.7 cm)
8. Place the hooked ends of the
other power supply cable wires
under the outer terminal block screws
(hook facing right). Squeeze hooked
ends together. Tighten screws.
Strip 5" (12.7 cm) of outer
covering from end of
Shape
ends
of
cable. Leave bare ground
wire at 5 inches. Cut 1-1/2"
(3.8 cm) from 3 remaining
wires. Strip insulation back
1 inch (2.5 cm).
wires
into a
hook.
9. Tighten strain relief screws.
10. Insert tab of terminal block cover
into slot of dryer rear panel. Secure
cover with hold-down screw.
Page 9
Three-wire connection...
Three-wire receptacle
Where local codes permit
POWER SUPPLY CORD
connecting cabinet-ground conductor to neutral wire:
4. Loosen or remove center
spade
terminal block screw.
terminals with
upturned ends
5. Connect the neutral wire (white
or center) of power supply cord to
the center, silver-colored terminal
screw of the terminal block.
Tighten screw.
ring
terminals
This blade connected
to this conductor.
6. Connect the other wires to
outer terminal block screws.
Tighten screws.
NEUTRAL
3/4" U.L.-listed
strain relief
NEUTRAL
(white or center)
7. Tighten strain relief screws.
Three-wire power supply cord must have
three, No.-10 copper wires and match a
three-wire receptacle of NEMA Type
10-30R.
8. Insert tab of terminal block
cover into slot of dryer rear panel.
Secure cover with hold-down
screw.
Where local codes permit
DIRECT WIRE
connecting cabinet-ground conductor to neutral wire:
Preparing the wire:
4. Loosen or remove center
terminal block screw.
Three-wire with ground wire:
Bare wire cut short. Wire is not
used. Dryer is grounded through
direct wire cable.
5. Place the hooked end of the
neutral wire (white or center) of
power supply cable under the center
screw of the terminal block (hook
facing right). Squeeze hooked end
together. Tighten screw.
3/4" (1.9 cm)
1" 2.5 cm)
of wires
U.L.-listed strain
stripped of
insulation
to
disconnect
box
6. Place the hooked ends of the
other power supply cable wires
under the outer terminal block
screws (hook facing right). Squeeze
hooked ends together. Tighten
screws.
NEUTRAL wire
10-gauge, 3-wire or,
10-gauge, 3-wire with
ground wire (Romex)
(white or center)
3-1/2" (8.9 cm)
Strip 3-1/2" (8.9 cm) of
outer covering from
end of cable. Strip
insulation back
1" (2.5 cm). If using
3-wire cable with
ground wire, cut bare
wire even with outer
covering.
7. Tighten strain relief screws.
8. Insert tab of terminal block cover
into slot of dryer rear panel. Secure
cover with hold-down screw.
Shape
ends of
wires into
a hook.
Page 10
Three-wire connection...
Three-wire receptacle
DIRECT WIRE OR
Where local codes Do Not permit
connecting cabinet-ground conductor to neutral wire:
POWER SUPPLY CORD
9. After reattaching the terminal
cover, connect a separate copper
ground wire from the external
ground connector screw to an
adequate ground.
Three-wire power supply cord must
have three, No.-10 copper wires and
match a three-wire receptacle of NEMA
Type 10-30R.
4. Remove center terminal block
screw.
5. Remove the appliance harness
ground wire (green with yellow
stripes) from the external ground
connector screw. Connect
appliance harness ground wire and
the neutral wire (white or center) of
the power supply cord/cable under
the center, silver-colored terminal
block screw. Tighten screw.
Direct wire power supply cable must be
prepared as shown in “Preparing the
wire” of the three-wire connection
direct-wire steps above.
If codes permit and a separate ground
wire is used, it is recommended that a
qualified electrician determine that the
ground path is adequate.
6. Connect the other wires to outer
terminal block screws. Tighten
screws.
7. Tighten strain relief screws.
8. Insert tab of terminal block cover
into slot of dryer rear panel. Secure
cover with hold-down screw.
7.To exhaust dryer, see Exhaust
requirements, Pages 3-4. Connect
exhaust vent to dryer exhaust outlet
and exhaust hood using 4" (10.2 cm)
clamps. Use caulking to seal exterior
wall opening around exhaust hood.
10.Check dryer operation (some
accumulated time may be on the
timer due to factory testing).
11.If drying time is too long,
make sure lint screen is clean.
12.Now start the dryer and allow
it to complete a full heat cycle (not
air cycle) to make sure it is working
properly.
Pull timer-set button left. (Operating
time will accumulate per number of
depressions and type of timing cam
used.) Push START/RESTART button.
Using a full heat cycle (not the air
cycle), let the dryer run for at least
five minutes.
8.Carefully move dryer into final
position. Place level on top of the
dryer, first side to side; then front to
back. If the dryer is not level, adjust
the legs of the dryer up or down until
the dryer is level.
Note: Dryer door must be closed for
dryer to operate. When door is open,
dryer stops, but timer continues to run.
To restart dryer, close door and push
START/RESTART button.
9.Plug power supply cord into
grounded outlet or connect direct
wire to power supply.
Turn power supply on.
Page 11
Electric dryer models:
Recessed area and
closet installation
instructions
Product dimensions
• Shut of electrical supply to dryer.
• Disconnect the power supply cord
or cable from the dryer terminal
block.
29" (73.7 cm)
This dryer may be installed in a
recessed area or closet. For recessed
area and closet installations,
16"
All models:
• Make sure leveling legs are secure
in dryer base.
• Tape drum to front panel.
• Tape dryer door, lint screen and
end of gas pipe.
(40.6 cm)
ELECTRIC
14-19/32"
minimum clearances can be found
on the serial tag on the dryer.
4"
(37.1 cm)
(10.2 cm)
dia.
28-1/4"
(71.8 cm)
The installation spacing is in inches
and is minimum allowable. Additional
spacing should be considered for
ease of installation, servicing and
compliance with local codes and
ordinances.
If closet door is installed, the minimum
unobstructed air openings in top and
bottom is required. Louvered doors
with equivalent air openings are
acceptable.
4-3/4"
GAS
EXHAUST
(12.1 cm)
Before the appliance is removed from
service or discarded, remove the
door to the dryer compartment.
18-3/8"
1-1/4" (3.2 cm)
(46.7 cm)
BACK VIEW
25-1/2" (64.8 cm)
If dryer does not
operate properly...
Companion appliance spacing
should be considered.
7-1/8"
(18.1 cm)
Check the following to be sure that:
35"
The dryer must be exhausted
outdoors.
1. Electric supply is connected.
2. Circuit breakers are not tripped or
house fuses blown.
(88.9 cm)
No other fuel-burning appliance may
be installed in the same closet.
3. Door is closed.
Minimum Installation Clearances
4. Controls are set in a running or
“ON” position.
5. Start button has been pushed
firmly.
SIDE VIEW
1"
(2.5 cm)
14"
(35.6 cm)
max.
6. For gas dryers, check that gas
supply shutoff valves are set in
open position.
Closet
15"
Maintenance
instructions
door
(3.8 cm)**
0"
(0 cm)*
• Clean lint screen after each cycle.
0" (0 cm)*
0" (0 cm)*
If you need
assistance...
• Keep dryer area clear and free from
combustible materials, gasoline and
other flammable vapors and liquids.
1" (2.5 cm)
Recessed
front view
Closet
side view
• Do not obstruct the flow of
combustion and ventilation air.
The Whirlpool Consumer Interaction
Center will answer any questions
about operating or maintaining your
dryer not covered in the Installation
Instructions. The Whirlpool Consumer
Interaction Center is open 24 hours
a day, 7 days a week. Just dial
1-800 NO BELTS (1-800-662-3587) —
the call is free.
Closet door
3" (7.6 cm)
Moving the dryer
48" sq.**
to a new location...
Slide dryer onto cardboard or
hardboard before moving across floor
to avoid damaging floor covering.
24" sq.**
When you call, you will need the dryer
model number and serial number.
Both numbers can be found on the
serial-rating plate located on your
appliance.
3" (7.6 cm)
Gas dryer models:
• Disconnect electrical cord. Tape
securely to dryer.
• Shut off the gas supply valves in the
gas supply line.
• Disconnect gas pipe and fittings
from dryer and cap gas supply line.
Tape end of dryer gas pipe.
Closet
front view
* Additional clearances for wall, door and floor
moldings may be required or if external
exhaust elbow is used.
** Opening is minimum for closet door. Louvered
door with equivalent air opening is
acceptable.
Part No. 8316557
© 2000 Whirlpool Corporation
Printed in U.S.A.
Prepared by Whirlpool Corporation, Benton Harbor, Michigan 49022
|